Bleed Airflow Measurement with Temperature and Alarm Capability
HTx104-B-Complete-System-0001
BTL_Logo
C UL US Listed
UKCA_Logo (002) copy

Advantage IV

Hybrid Series
HTX104-B
Bleed Airflow Measurement with Temperature and Alarm Capability

The HTx104-B is a unique measurement device that can detect very small pressure differentials (as low as 0.0002” H2O) between two adjacent spaces by sensing the airflow rate induced by the pressure gradient. The HTx104-B can be used to determine the airflow rate across fixed openings when a reference airflow rate is provided. More output circuit protection than the EF-x2000-B with a true 4-20mA output option (HTA104-B) make this the best choice for these applications.

  • Thermal Dispersion Technology
  • Bi‐directional Airflow Measurement
  • Detect ΔP as low as 0.0002″ H₂0
  • Optional Mounting Kits Available
  • Airflow (or ΔP) and Status Alarm
  • Temperature Output Capability
  • Analog and RS‐485 Output Models
  • 1/2″ NPT Female Pipe Connections
  • Remote Transmitter with LCD Display
  • 3‐year Warranty

Typical Applications

  • Ultra-low Differential Pressure Detection
  • Parking Garage Pressurization
  • Construction Zone Contaminant
  • Stairwell Pressurization
  • Relief and Exhaust Damper Control
  • Airflow across a Louver or other Fixed Opening

Benefits

  • Maintain Pressure Relationships between Adjacent Spaces
  • Satisfy LEED Prerequisites and Credits
  • Provide Acceptable IAQ
  • Save Energy
  • Reduce Liability
  • Improve Performance

Product Highlights

  • Uni- or Bi-directional Measurement
  • Extremely Sensitive
  • Airflow or Equivalent Pressure Output
  • Long-term Stability
  • Small Footprint
  • Simple NPT Pipe Connections
  • Optional Mounting Kits Available

General

Probe and Sensor Node Configurations

1 bi-directional, dual 1/2” NPT female bleed sensor housing

Installed Airflow Accuracy

Airflow through an opening or across and obstruction: Requires field measurement of a reference airflow of the specific installation.
The Field Adjust Wizard (FAW) facilitates setup.
Equivalent pressure between two adjacent spaces: Requires field measurement of a reference pressure to correct the default flow
coefficient of the specific installation. The Field Adjust Wizard (FAW) facilitates setup.

Listings and Compliance

UL: UL-873 and CSA C22.2 No. 24;
CE: Non-UK European shipments only
UKCA::UK shipments only
BACnet International::BTL Listed (HTN104 transmitter)
FCC: This device complies with Part 15 of the FCC rules
RoHS: This device is RoHS2 compliant

Environmental Limits

Temperature:
Sensor:  -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]
Transmitter: -20 to 120 ⁰F [-28.9 to 48.9 C]
Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%

Bleed Sensor Assembly

Sensing Node Sensors

Self-heated sensor: Two precision, hermetically sealed, bead-in-glass thermistor probes
Temperature sensor: One precision, hermetically sealed, bead-in-glass thermistor probe

Sensing Node Housing

Material: Glass-filled Polypropylene
Sensor Potting Materials: Waterproof marine epoxy

Airflow Measurement

Accuracy: ±2% of reading to NIST-traceable airflow standards (includes transmitter uncertainty)
Calibrated Range: -3,000 to 3,000 fpm [-15.24 to 15.24 m/s]
Calibration Points: 9

Temperature Measurement

Accuracy: ±0.15 ⁰F [0.08 ⁰C] to NIST-traceable temperature standards (includes transmitter uncertainty)
Calibrated Range: -20 to 160 ⁰F [-28.9 to 71.1 ⁰C]
Calibration Points: 3

Probe to Transmitter Cables

Type: FEP jacket, plenum rated CMP/CL2P, UL/cUL listed, -67 to 302 ⁰F [-55 to 150 ⁰C], UV tolerant
Standard Lengths: 10, 25 and 50 ft. [3.1, 7.6 and 15.2 m]
Connecting Plug: 0.60” [15.24 mm] nominal diameter

Transmitter

Power Requirement: 24 VAC (22.8 to 26.4 under load) @8V-A
User Interface: 16-character LCD display and 4 button interface

B.A.S. Connectivity Options

HTA104 Transmitter: Two field selectable (0-5/0-10 VDC or 4-20mA), scalable and isolated analog output signals (AO1=airflow, AO2=temperature or alarm)
HTN104 Transmitter: One field selectable (BACnet MS/TP or Modbus RTU) and isolated RS-485 network connection- Individual sensor node airflow rates and temperatures are available via the network

Airflow (or Pressure) Alarm

Type: Low and/or high user defined setpoint alarm
Tolerance: User defined setpoint value
Delay: User defined
Reset Method: Manual or automatic
Visual Indication: Yes, LCD display
Network Indication: Yes (HTN104 only)
Analog Signal Indication: Yes, on AO2 assignment (HTA104 only)

System Status Alarm

Type: Sensor diagnostic system trouble indication
Visual Indication: Yes, LCD display
Network Indication: Yes (HTN104only)
Analog Signal Indication: Yes, on AO2 assignment (HTA104 only)